Did You Actually Test Every Heat Strip - Short #311
· Summarized
Key takeaways
- Warm supply air or a running blower does not prove that every auxiliary heat-strip bank is operating; each circuit must be tested during an actual electric-heat call.
- Never assume an existing heater kit is correctly matched to its breakers, wiring, relays, or wire size; a five-kilowatt bank draws about 20.8 amps at 240 volts.
- Allow sequencers to complete their intended timing, keep thermal limits and fusible links in place, and ensure the blower interlock makes the blower run with the strips—not the reverse.
- The practical verification is to measure each bank’s current, confirm the blower operates, and confirm current stops when the heat call ends.
Summary
Why warm air does not prove every heat strip works
The host explains that in Florida, electric heat is usually auxiliary heat for a heat pump rather than full emergency heat; colder markets may instead use a furnace in a dual-fuel system. Turning the thermostat to heat and feeling warm supply air can prove only that the heat pump is operating or that one of several heat-strip circuits works. A second strip may be disconnected, or the auxiliary heat may fail unnoticed until outdoor temperatures fall or the heat pump enters defrost. The correct test must identify which circuits actually energize.
The host’s five-kilowatt wiring mistake
The host recalls finding a roughly 10-kilowatt electric heater in an older Wintermere home with five kilowatts disconnected. He reconnected the unused bank, then noticed that the high-voltage wiring had been sized only for the original five kilowatts. The previously unused elements were also extremely dirty; when energized, they nearly smoked up the house and alerted him to the problem before he left. He warns that a technician cannot assume the installed kit, breaker, wiring, or wire size is correct, even when merely replacing an air-handler box.
Why heater ratings change with voltage
Electric heaters are resistive loads that draw steady current. A five-kilowatt bank applied with 240 volts draws about 20.8 amps, roughly 20 amps, which the host compares to the substantial load of a compressor. The same heater’s resistance does not change when supplied with 208 volts, so its output falls to about 3.76 kilowatts and current to about 18.1 amps. Conversely, higher utility voltage increases both current and wattage; the host says technicians increasingly encounter supplies in the 250–253-volt range. Nameplates may list both 208- and 240-volt ratings.
How heat calls, interlocks, and sequencers behave
Electric heat may be energized by a thermostat’s W call when the heat pump cannot maintain indoor temperature, or by the outdoor defrost control calling through the white wire. A blower interlock should ensure the blower runs whenever heat strips are energized, but the blower running should not prove that the strips work. Incorrectly bypassing an old high-voltage relay can make strips run whenever the blower runs and can overload relay contacts. Thermal limits or fusible links must remain in the circuit. Older sequencers also delay and stage contacts rather than closing instantly, so technicians must wait for the intended sequence.
The recommended strip-by-strip test
The host recommends identifying the installed heat kit, forcing an actual electric-heat call, allowing time for any sequencer delay, and measuring current on each bank. Each five-kilowatt bank should draw approximately its rated current, with only minor variation between similar banks; current should disappear when the call is removed. The technician should verify that the blower operates during the heat call as well. Resistance measurements can confirm continuity, but hidden thermal safeties or fusible links may be open, so suspected elements should be inspected directly. Multiple incoming power supplies and breakers must all be de-energized before service.
Temperature rise and maintenance cautions
As a rough sea-level example, 10 kilowatts equals about 34,100 BTU per hour and produces approximately a 32-degree temperature rise at 1,000 CFM; half the output produces roughly half the rise. The host says this calculation is sensitive to airflow and temperature-measurement accuracy, making a TrueFlow grid preferable for airflow work. Heat-pump capacity must be checked in heating mode with strips off. During fall maintenance, technicians should warn customers about odor, inspect or gently clean dirty strips with low-pressure compressed air or electrical contact cleaner, and never rub the fragile elements or burn heavy contamination off inside the house.
Sponsors
- Refrigeration Technologies · The host promoted the Viper Wet Rag Heat Shield, a flame-resistant welding pad that can be used wet or dry, and directed listeners to find it through a distributor or use the GETSCHOOLED discount code at TrueTechTools.com.
- Carrier · The host mentioned Carrier’s GreenSpeed Extreme high-efficiency heat pumps and directed listeners to Carrier’s website for more information.
- White-Rodgers · The 50M5X-843 universal single-stage furnace control replaces more than 500 PSC and ECM/X13 control part numbers without additional harnesses. It detects the OEM harness, works with the White-Rodgers Connect app through near-field communication, and includes AutoSet and manual configuration features.
- Santa Fe · Santa Fe’s new Total Peace of Mind warranty provides customers with five years of complete replacement coverage plus an additional year for parts.
Show notes
In this short podcast episode, Bryan talks about electric heat and whether your service or maintenance procedure actually allows you to test every heat strip. In our climate, we use electric heat as auxiliary heat (as opposed to a furnace in a dual-fuel setup). There is also some information about maintenance procedures, blower interlocks and relays, and math to determine amperage.
If you put the thermostat in heat and the blower runs, you only prove that the heat pump is heating; it doesn't tell you which electrical circuit is heating, or whether the auxiliary heat is producing heat at all. You can't assume that the last tech left you the correct kit with everything wired up and that it has been wired properly with the correct wire size.
Electric heaters in heat pumps usually turn on with a W call from the thermostat or the defrost board. Sometimes, there is a high-voltage interlock with a relay that runs the blower with the electric heat but not the other way around. Older heat strips may also have heat sequencers, which follow a specific sequence and stage on or off over time.
We test heat strips by forcing a call for heat, waiting as long as needed, measuring the amperage to make sure it matches the heat kit, making sure the blower comes on, and verifying that the call for heat ends as it's supposed to. Temperature rise may also be a useful measurement. If a similar procedure is part of your fall maintenance, let the customer know that there may be an odor, and you may clean dirty heat strips with compressed air or an electrical contact cleaner.
The key takeaway is to make sure the amperage is correct and that the circuit's wiring and relays can safely carry the current. Don't assume that everything is correct when you work on a unit for the first time.
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Copeland, and Santa Fe Dehumidifiers.
Resources
- An Electric Heat Mistake (Tech Tip)
- Electric Heat & Blower Interlock (Tech Tip)
- Electric Heat Troubleshooting, Service, and Math Class (Video)
- Basics of Testing Electric Heat Kits w/ Bert (Video)
- Inside a Sequencer (Video)
- Sequencer Facts - They Aren't All the Same (Video)
- Relays, Sequencers, Transformers, and Bad Metaphors (Podcast)
- HVAC School calculators
- Submit a podcast question
- Learn about the GRIT Foundation
Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Follow this show on AudioBrevity and new episodes get summarized for you. Create a free account