HVAC School - For Techs, By Techs

It Lit. That Doesn't Mean You're Done - Short #313

· Summarized

Share this episode
Anyone with this link can open it.
Share Link
Start at 0:00

Key takeaways

  • A furnace lighting only proves ignition; technicians must observe the entire sequence, including blower startup and operation after several minutes.
  • Pressure-switch and limit-switch states are clues to investigate, not permission to replace parts or bypass safeties without finding the underlying condition.
  • Gas pressure does not by itself establish correct fuel input; meter clocking, fuel heating value, proper corrections, and the nameplate rating also matter.
  • Temperature rise must be measured with representative, stabilized air temperatures, because coil thermal mass can temporarily conceal excessive heating.
  • Safe commissioning requires combustion analysis, personal CO monitoring, airflow verification, inspection of condensate and burners, and visual checks of every flue and termination.

Summary

Ignition Is Only the First Furnace Checkpoint

Bryan opens by arguing that a furnace service call or installation is not finished when the igniter glows and the burners light. The unit still has to deliver heat through the air-distribution system while combustion and venting remain safe and functional. He recommends observing the complete sequence: the call for heat, control checks, inducer operation, pressure-switch closure, ignition, flame proving, and the delayed start of the main blower. What happens immediately after the blower starts—and several minutes later—can reveal faults that “it lit” would miss.

Use Measurements and Do Not Bypass the Safeties

Bryan says the ideal commissioning setup includes inlet and outlet gas-pressure measurements, furnace temperature-rise measurement, combustion analysis, and a low-level personal CO alarm, preferably one with a display to detect spillage. Brief ignition followed by shutdown, flame loss when the blower starts, or burners dropping out while the blower continues point to different investigations, but none proves a failed part. He warns never to bypass a pressure switch or limit; verify its state with a meter and determine what condition caused it.

A Safety Switch’s State Is a Clue, Not a Diagnosis

If a pressure switch will not close, Bryan says to investigate blocked flues—including a squirrel or bird—water around a secondary heat exchanger, or water entering the switch. If a limit is open, it may have opened because of overheating rather than failed on its own. Start with airflow: a blocked filter, dirty coil or blower wheel, restricted secondary heat exchanger, closed supply registers, incorrect airflow taps, or inadequate ductwork can all cause limit cycling. TrueFlow-grid airflow checks and temperature-rise measurements can expose low airflow before the limit trips.

Confirm the Furnace’s Actual Fuel Input

The furnace nameplate identifies the intended fuel type and input, but Bryan says gas pressure alone does not prove that the fuel type, orifices, available pressure, or fuel heating value are correct. On a conventional natural-gas system, clocking the meter can provide an input check, provided other appliances are not using gas and pressure and temperature corrections are applied. If an 80,000-BTU-input furnace appears substantially overfired, he says to recheck the math rather than speeding up the blower to conceal the resulting temperature rise: “check yourself before you wreck yourself.”

Temperature Rise Must Stabilize Before You Judge It

Temperature rise is the difference between return air entering the furnace and supply air leaving it, measured with representative air temperatures rather than a probe aimed at a hot heat exchanger. A 70°F return and 120°F supply produce a 50°F rise, acceptable for a furnace rated from 40° to 60°. But if the supply eventually reaches 140°F, the 70° rise is excessive; an evaporator coil’s thermal mass may briefly hide the problem. Bryan favors the lower side of the rated range and recommends checking filters, coils, blower condition, airflow setup, furnace taps, and ductwork.

Combustion, Shutdown, and Venting Still Need Inspection

A blue flame does not establish safe CO or correct flue-gas oxygen, so Bryan recommends a properly prepared combustion analyzer and a correct sampling point; a flame or combustion-reading change when the blower starts is not automatically a cracked heat exchanger. On condensing furnaces, verify condensate drainage and piping. During shutdown, confirm the gas valve closes without loud pops, check burner alignment and flame channels, and monitor for spillage. Inspect every flue, its heat damage and joints, attic and outdoor terminations, possible recirculation into outdoor-air intakes, and depressurization around open-combustion furnaces.

Sponsors

  • Refrigeration Technologies · Bryan promotes Viper Wipes as an all-purpose wipe that cuts through mastic, oil, grease, tar, and grime while being gentle on the hands.
  • Carrier · Bryan mentions Carrier’s GreenSpeed Extreme high-efficiency heat pumps and directs listeners to the company website.
  • NAVAC · Bryan highlights the Nexus NX1 and NX4 digital manifold gauges. The NX1 supports 72 refrigerant types, including A2Ls, handles 600 PSI, and has quarter-turn ball valves. The NX4 adds four valves and a three-quarter-inch vacuum port, with manifold, leak-test, evacuation, and decay-test modes, plus integration with the NMV1S micron gauge and MyNAVAC app.
  • Fieldpiece · Bryan promotes the CAT85 Combustion Analyzer, which measures O2, CO, CO2, and draft pressure, includes a built-in manometer, automatically removes water through HydroCycle pump technology, uses replaceable sensors with a four-year warranty, and connects to JobLink with a 1,000-foot wireless range.
  • Filtrete · The episode is identified as being brought to listeners by Filtrete Air Filters.

Show notes

In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, and the furnace still needs to deliver heat and vent flue gases safely.

The key takeaway here is that if we only focus on making sure "it lit," we could miss overfiring, poor air delivery, intermittent limit problems, or venting problems. We want to be able to observe the complete sequence of operations. What happens when the blower starts is useful information, as is what happens when it's been running for several minutes.

Fuel input also matters. The furnace nameplate tells you which fuel type a system is designed for, as well as the gas pressure readings and the temperature rise. The BTU value of the fuel also matters, which you can determine by clocking the gas meter, and then our temperature and pressure corrections will also be important factors.

When commissioning a gas furnace, we should measure gas pressure and temperature rise (the increase between return air entering the furnace and the supply air leaving it), perform combustion analysis, and wear a low-level personal CO monitor. We can also verify airflow with a TrueFlow grid. We should also NOT bypass safeties at any point; we should check any safeties with a meter and investigate why they're behaving a certain way. Temperature rise and airflow problems may also point us toward some common issues, including easily fixed ones like dirty filters and systemic issues like poor ductwork.

Other things to watch include shutdown, condensate removal (for high-efficiency furnaces), burner alignment, all flue assemblies (visual inspection, termination points, and monitoring CO spillage), and the likelihood of depressurization.

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, Fieldpiece,  and Filtrete.

Resources

Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Follow this show on AudioBrevity and new episodes get summarized for you. Create a free account

Couldn't load the audio. A blocker may be stopping the show's tracking links. Open the file