HVAC School - For Techs, By Techs

Uncovering the Root Causes of Commercial Refrigeration Failures

· Summarized

Share this episode
Anyone with this link can open it.
Share Link
Start at 0:00

Key takeaways

  • Transcritical CO2 systems introduce high-pressure and high-ambient challenges, and Florida’s heat combined with humidity can reduce the effectiveness of adiabatic cooling.
  • A built-up refrigeration system may first receive its real stress test during field installation and startup, so technicians must verify the work rather than assume factory documentation is correct.
  • Nitrogen purging, clean brazing, deburring, and proper cleanup prevent copper oxide and debris from restricting tiny orifices, ejectors, valves, and microchannel equipment.
  • When racks, condensers, and controllers come from different manufacturers, programming often has to be tuned for the individual store and verified with all parties.
  • High dew point, failed dehumidification, and airflow from ceiling fans or doors can cause case icing and sweating even when the refrigeration circuit itself is operating correctly.
  • Technicians should follow the root cause all the way from complaint to verified corrective practice instead of stopping after a parameter change, part replacement, or temporary symptom fix.
  • The team recommends sharing field knowledge, checking fundamentals, documenting expectation and design conflicts, and designing equipment for worst-case conditions rather than merely a stated design day.

Summary

Christian and Alex introduce the market-refrigeration problem

Host Brian Orr introduces a Kalos co-branded livestream with Christian Maitland and Alex Orr, members of his market-refrigeration team. Christian has worked at Kalos for about six years and focuses largely on supermarket equipment and startup work; Alex, Brian’s son, moved from residential and other trades into supermarket demand service after roughly five to six years with Kalos. The stated subject is finding root causes instead of repeatedly treating symptoms. Brian jokes that the team can repair complicated machinery but still struggled to launch the livestream, establishing the informal tone before turning to new grocery-store equipment.

Transcritical CO2 brings unfamiliar behavior to U.S. stores

Christian says transcritical CO2 is expanding from Europe into the United States, but manufacturers are implementing it differently and are still learning what works. Above roughly 86°F, CO2 no longer behaves like a conventional multiphase refrigerant along the familiar saturation curve, making high-ambient operation less efficient but still possible. Manufacturers often use adiabatic, or evaporative, cooling to manage the high side; Christian and Brian point out that Florida’s combination of heat and high relative humidity limits that strategy. Alex adds that the system’s high pressures remain intimidating, especially when failures produce loud releases.

Controllers can take down a rack and waste its charge

The team discusses newer controllers that overheat, reset, and take refrigeration offline. When a controller reboots, it may take about 30 minutes, while a store may have only around an hour—depending on ambient conditions—before losing its CO2 charge and then requiring several more hours to restore cooling. Brian says the problem is often an interface failure: the rack, condenser, and controller may each be good products, but they were not adequately tested together. Christian adds that technicians transitioning from DX must learn that venting or purging CO2 can be an intended safety response, whereas allowing pressure to approach 1,800–1,900 psi is dangerous.

Startup technicians learn to question both installers and manufacturers

Christian says his major management lesson was learning not to assume every failure was an installation mistake. His startup team increasingly finds problems in firmware, programming, wiring, documentation, or factory assembly, then has to explain previously unknown failures to manufacturers. Examples include incorrectly wired harnesses, sensors landed on the wrong terminals, and a transcritical condensing unit whose condenser fan would not run because two sensors had been swapped. Using a signal generator to force the fan on helped expose the issue; the manufacturer then notified other projects because roughly 60 units had the same problem.

Dirty brazing practices create expensive restrictions

Brian and Christian identify piping workmanship as a recurring failure source, particularly when technicians skip nitrogen purging, leave burrs, or allow copper-oxide debris to form inside the system. Large pipes require more torch time, and newer equipment may contain microchannel coils, tiny orifices, or ejectors that are easily restricted by carbon buildup. Christian says these mistakes add labor to an already difficult commissioning process. Alex and Brian recount separate incidents involving internal plugs in ACR copper: Alex’s plug eventually shot out and smoked a grocery-store liquor section, while Brian discovered his own plug lodged in an EPR after completing an early walk-in project.

Built-up controls require programming for each store

Christian explains that a rack may be manufactured by one company, its condenser by another, and its BAS or EMS controller by a third. Each product can work correctly under its maker’s assumptions while failing when the other pieces behave differently. Because racks are configured for individual sites—with different compressor counts, valves, and case loads—startup technicians compare the bid set, prints, delivered equipment, customer expectations, and actual programming, then work with multiple manufacturers to create or revise parameters. Brian warns against casual field “software tweaking”: startup should establish the correct settings, while later changes should follow a verified diagnosis.

Case placement and store humidity can defeat good refrigeration

Alex says the most common post-startup failures are often environmental rather than mysterious controller faults. High store dew point, a nonworking dehumidifier, or ceiling fans blowing into an open case can destroy the air curtain, causing icing, sweating, and failure to maintain temperature. One beer case had a fan blowing into it while humidity was high; condensation soaked cartons until customers pulled them apart and spilled beer. The group also cites an open case installed beside a convenience-store entrance, despite manufacturer warnings, because every door opening introduces humid drafts. Smoke pens and vane anemometers can reveal these airflow problems.

The root-cause method goes beyond making the symptom disappear

Brian describes the team’s process as the scientific method: observe the complaint, form a hypothesis, test it, identify the actual cause, and verify that the corrective practice prevents recurrence. Removing a clogged screen may restore flow, but the deeper cause could be copper oxide from inadequate nitrogen purging; the team must then correct brazing and cleanup practices and inspect later systems. Alex applies the same standard to frozen cases, saying technicians should determine whether programming, training, unfamiliar equipment, or communication caused the failure rather than merely de-icing and leaving. Christian says documentation and peer training make the fix repeatable.

A confident transducer diagnosis still missed a wiring fault

Alex recounts diagnosing a dehumidifier at a store where sweating doors and a dew point around 62°F indicated poor dehumidification. He found a transducer output that did not match pressure and ordered a difficult-to-source replacement, which took about three weeks to arrive. The replacement changed nothing because the signal passed through a redundant unloader controller; that controller was dropping roughly 0.5 volts DC. Alex eventually bypassed the unnecessary connection and restored operation in seconds. The story taught him to eliminate every alternative before ordering long-lead parts, even when 95% of the initial diagnosis appears convincing.

Lead times, commissioning, and worst-case design shape the final advice

Christian says new equipment creates unplanned labor because technicians are learning alongside manufacturers, sometimes spending hours finding the right support person or part. Alex describes an unloader that arrived correctly only on the seventh attempt after roughly eight weeks, while construction managers called late at night demanding progress. Live-store case swaps make commissioning harder, and manufacturer training may not exist before installation. The team’s closing advice is practical: use your senses on the first walkthrough, verify line sizing and case assembly, pull proper vacuums, share information with peers, and design equipment for worst-case conditions rather than a nominal design day. Christian calls peer learning essential; Alex says solving ridiculous failures is the job and a chance to be the hero.

Sponsors

  • Refrigeration Technologies · The sponsor promotes the Viper Wet Rag Heat Shield, a flame-resistant welding pad usable wet or dry. Listeners can find it through distributors or receive a discount with offer code GETSCHOOLED.
  • Carrier · Carrier is mentioned as a sponsor without an additional product message.
  • Copeland and White-Rodgers · The White-Rodgers Hot Rod Combo, model 21D64C-843, combines a universal 120-volt nitride hot-surface igniter and universal flame sensor. Each replaces more than 150 OEM parts, making the kit useful for truck stock. The sensor can be cut and bent for fit, and the igniter is described as stronger and less corrosion-prone than silicon carbide.
  • Santa Fe Dehumidifiers · Santa Fe promotes its dehumidifiers and a new warranty offering: five-year complete replacement coverage plus an additional year for parts. The ad also emphasizes whole-house ventilating dehumidifiers, humidity control near 50%, and protection against mold, dust mites, wood rot, and pests.
  • TruTech Tools · TruTech Tools offers more than 90 brands, field-experienced technical support, industry training, downloadable worksheets, and shipping to all 50 states and U.S. territories. The sponsor repeatedly promotes offer code GETSCHOOLED and highlights tools, books, and resources for HVACR technicians.

Show notes

In this live stream, co-branded with Kalos, Bryan Orr sits down with Kalos refrigeration team members Christian Maitland and Alex Orr to talk about the realities of working on market refrigeration systems. The conversation starts with the rapid arrival of new equipment in grocery stores, especially transcritical CO2 racks, and why even well-trained techs are running into problems nobody has seen before. Because these are engineered, built-up systems rather than mass-produced units, the first real stress test often happens in the field, during installation and startup.

The group digs into where those problems actually come from. Some are classic installation errors, like skipping nitrogen purges while brazing, leaving burrs in pipe, or forgetting that ACR copper plugs sit on the inside of the pipe. Others trace back to the manufacturer: sensors landed on the wrong terminals, swapped sensors that left a condenser fan unable to run, controllers that overheat and reset, and programming that was tested in a different climate than the one the equipment ends up in. With multiple manufacturers supplying the rack, controller, and condenser, nobody owns the interface between the pieces, so startup techs end up tuning parameters store by store.

Bryan, Christian, and Alex also walk through the root cause process they rely on, which is essentially the scientific method: observe the complaint, form a hypothesis, test it, and then keep digging until you know why it happened and can confirm the fix on the next job. They discuss store dew point and airflow as the most common causes of iced-up and sweating cases, a humbling misdiagnosis involving a transducer and a redundant controller, and the pain of 19-week lead times and wrong parts arriving seven times in a row.

The episode closes with practical advice for techs. Walk into every store and use your senses, check behind your install team, pull your vacuums, and document conversations with customers when expectations don't match the equipment specs. Christian encourages techs to share what they learn with peers, Alex reminds listeners that solving ridiculous problems is the job and a chance to be the hero, and Chad's late addition is a reminder that equipment should be designed for worst-case conditions rather than a design day.

Topics Covered

  • Transcritical CO2 coming to the U.S. market, and why it behaves differently above roughly 86°F
  • Challenges of high ambient temperature and humidity in Florida, including limits of adiabatic cooling
  • Controllers that overheat and reset, and how quickly a CO2 system can lose its charge when that happens
  • Safety and mindset for techs moving from traditional DX to high-pressure CO2 systems
  • Why built-up systems get their first real field test at installation and startup
  • Clean piping practices: nitrogen purging, burrs, carbon buildup, and tiny orifices in ejectors and microchannel coils
  • The pipe plug in the EPR story and other lessons from early grocery work
  • Manufacturer errors caught at startup, including miswired harnesses and swapped sensors
  • Interconnected controls from different manufacturers and the need for site-specific programming
  • Setting customer expectations on case placement, shelving, and spec limits, and documenting those conversations
  • Store dew point, dehumidifiers, and ceiling fans disrupting open-case air curtains
  • Using building science tools like smoke pens and vane anemometers on refrigeration cases
  • The root cause process: observe, hypothesize, test, find the real cause, and verify the fix
  • A transducer misdiagnosis and why to rule out everything before ordering long-lead-time parts
  • Parts lead times, wrong parts, and the hidden labor cost of learning new equipment alongside manufacturers
  • Commissioning during live-store case swaps, and the gap in manufacturer training for new equipment
  • What techs look for on a first walkthrough, plus startup checks like line sizing, case assembly, and pulling vacuums
  • Gaps in tools, such as digital gauges built for transcritical systems
  • Closing takeaways: share knowledge with peers, own the problem, and design equipment for worst-case conditions

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Copeland, Santa Fe Dehumidifiers, and TruTech Tools.