Tight Enough to Fail - Short #309
· Summarized
Key takeaways
- A screw that feels tight can still have poor electrical contact, increased resistance, and unwanted heating.
- With resistance held constant, doubling current produces four times the heating power at a connection because heating follows current squared times resistance.
- A hot terminal in a thermal image is evidence that deserves investigation, but current, comparable loads, warm-up time, and other operating conditions are needed to determine the cause.
- Over-tightening can damage threads, screw heads, or terminal components, so applying more force is not a reliable way to repair a bad connection.
- Use the manufacturer’s torque specification, the correct torque units, and the correct driver bit; 40 inch-pounds is not the same as 40 foot-pounds.
- Correct wire size and material, strip length, conductor placement, seating, authorized wire count, terminal type, and proper crimping matter just as much as the tightening force.
- Electrical termination work should be performed safely with power off, and technicians should not assume that every overheating problem is caused by a loose connection.
Summary
A tight screw is not automatically a good electrical connection
Brian opens by asking whether electrical connections are always better when they are tighter, then answers that they are not. He describes a familiar maintenance routine: opening a panel, putting a screwdriver on every terminal, wiggling spade connectors, and giving each Phillips-head screw an extra snug turn. His point is that a screw turning does not reveal how much force has actually been applied or whether the conductor is making good contact. He defines torque as a turning effect—the force applied at a distance from the center of the screw. A quarter-turn is therefore not a measurement of the force applied. If a terminal or screw shows discoloration even though the wire is still present and the screw feels tight, Brian says it deserves closer investigation rather than automatically receiving another turn. A connection can be mechanically tight and still electrically poor. The important result is low resistance to current flow; poor contact can increase resistance at the connection and create unwanted heat.
Why a poor connection can become dangerous under load
Brian connects the heating problem to Watt's law: current squared times resistance. With resistance held constant, doubling the current produces four times the heating power at that connection. This explains why a connection may appear uneventful under a light load but reveal a much larger problem when the equipment draws more current. He cautions that real connections do not always follow a perfectly neat pattern as they heat. Resistance and other operating conditions can change, just as the resistance of a tungsten light-bulb filament increases as it heats. For that reason, a thermal image of a hot terminal is useful evidence but does not, by itself, identify the cause. The technician also needs to know what current is flowing, compare similar connections under similar loads, and allow the equipment enough time to warm up. Temperature should prompt an investigation, not be treated as a diagnosis on its own. Brian also notes that an overloaded circuit can damage an otherwise good connection over time, so overheating does not prove that the connection was loose.
Over-tightening can damage the terminal instead of fixing it
Brian asks why a technician should not simply “twist the sucker” tighter. His answer is that terminals and their parts have limits, and some technicians are strong enough to damage threads, heads, or other hardware by applying excessive force. He recalls his father calling this “McGilligoring” something and imitates the much less technical “uga buga” approach to over-tightening. The extra force can make the original problem worse, and a torque tool cannot undo damage that has already been done. He recommends using a torque screwdriver, while acknowledging that not everyone will use one on every routine residential maintenance visit. Using one at least sometimes helps technicians develop a sense of what the correct amount of tightening feels like. He emphasizes that correct torque is often less than people expect. The tool must be set using the manufacturer’s actual specification and the correct bit. Brian also warns about units: residential work commonly specifies inch-pounds, while larger commercial or industrial work may use foot-pounds. Since 12 inch-pounds equal one foot-pound, setting a tool to 40 foot-pounds when the instruction calls for 40 inch-pounds applies 12 times the intended torque and could break the connection.
Wire size, placement, terminals, and preparation matter as much as torque
For a new connection, Brian says the technician must consider more than how tightly the screw is turned. The terminal must be intended for the conductor’s size and material. An incorrectly oversized or undersized wire, unauthorized multiple wires or double-lugging, incorrect strip length, excess exposed conductor, or insulation left in the wrong place can all create problems. He specifically points out that some terminals have a plate beneath the screw, and the wire belongs under that plate rather than directly under the screw head. The conductor must be fully seated, and technicians should be suspicious of unapproved substances or “weird goo” placed in the terminal. Ferrules, spade terminals, and ring connectors must be correctly selected for the expected current and properly crimped; changing the wire’s shape with a barrel or ferrule does not remove the need to follow the terminal’s instructions. Spring terminals have no screw to torque, but they still require the correct wire size, strip length, and insertion. Brian’s overall advice is to use “Spidey Senses” before turning anything: inspect the whole termination rather than assuming that a wire fitting, a spade being attached, or a conductor being under a screw means the connection is correct.
Use manufacturer data, work safely, and do not turn a rule of thumb into a rule
Brian says the best starting point for a new connection is the actual torque specification on the equipment label or in the installation instructions. If the specification is not immediately available, technicians should look up the manufacturer’s information, especially when working on unfamiliar equipment. He also notes that commercial and industrial environments may have explicit inspection or retorquing procedures, with much higher stakes than an ordinary residential service call. All termination work should be done with the power off and without voltage present. Brian does not claim that every residential technician must retorque every terminal on every visit, nor does he present an older HVAC School torque-check practice as a universal instruction. Instead, he says rules of thumb are intended to encourage better practices, while high-stakes industrial work requires exact compliance. A torque screwdriver is relatively inexpensive and helps establish what “good” looks like. He closes by repeating that tightening a connection does not necessarily improve it, and that both the physical installation and the electrical operating conditions must be investigated.
Sponsors
- Refrigeration Technologies — Viper Wipes · The host describes Viper Wipes as an all-purpose wipe that can cut through plastic, oil, grease, tar, and grime while remaining gentle on the hands. He jokes that the wipes leave your hands soft enough to go home and go dancing.
- Carrier · The host says Carrier has been a long-term sponsor that helped make the podcast possible early on. He highlights Carrier products ranging from single-stage equipment to the GreenSpeed Extreme, which he calls one of the most efficient products on the market, and directs listeners to learn about Carrier products and becoming a dealer.
- Filtrete · The sponsor message explains that Filtrete filters display a MERV rating and an NPR, or Micro Particle Performance Rating, indicating how well they capture tiny particles such as smoke and bacteria. Filtrete's pleated media is said to maintain similar airflow across MERV 8, 11, and 13 ratings. The host cites California Energy Commission data saying Filtrete's 1900 NPR MERV 13 filters have the highest airflow rating among available residential one-inch MERV 13 filters.
- AHR Expo 2027 · The host announces that the 2027 AHR Expo will be held at McCormick Place in Chicago from January 25 through 27. Listeners can see HVACR tools and technology and attend live podcasts, including the host's, and are encouraged to register.
Show notes
In this short podcast episode, Bryan discusses electrical connections and whether tighter is better (or if a connection is tight enough to fail).
Torque is a turning effect; force is applied at a distance from the screw's center, and that force creates pressure at the connection. A quarter-turn doesn't tell us how much force we have applied. You may notice a tight screw with other signs of a poor connection, like discoloration; tightening the connection may not help.
At a connection, we want very little resistance to current flow, and we get increased resistance and heat where we don't want it when connections are poor; according to Watt's law, when the resistance stays the same, doubling the current creates four times the heating power. However, temperature alone doesn't tell you the cause; thermal imaging is useful evidence, but we need operating conditions and current measurements, too.
The key takeaway is that tightening the connection as much as possible may do more harm than good; having a torque screwdriver and using it can help. When making new connections, use the torque screwdriver to torque to the proper specs right out of the gate. We must also consider wire sizing, wire placement, exposed conductors, and unacceptable double lugging. We must also be mindful of ferrules, including proper selection and crimping. Make all adjustments safely (without voltage), and if you do not have the manufacturer's data immediately available, look it up. Eventually, you will get an idea of what "good" looks like.
Remember: tighter doesn't necessarily mean better.
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, Filtrete, and the 2027 AHR Expo.
Resources
- Tightening Electrical Threaded Terminal Connections (tech tip)
- HVAC School calculators
- Submit a podcast question
- Learn about the GRIT Foundation
Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Follow this show on AudioBrevity and new episodes get summarized for you. Create a free account