Dew You Get the Point — Tim De Stasio and Sophie Ashley
· Summarized
Key takeaways
- Relative humidity is temperature-dependent and can conceal the actual moisture content; dew point is a more direct way to compare moisture between air samples at different temperatures.
- A practical summer indoor target is 75°F dry bulb with approximately a 55°F dew point, while sustained conditions above 60% RH or a 60°F dew point are warning signs.
- At an evaporator, supply dew point should be lower than return dew point and generally within about three degrees of supply dry-bulb temperature, indicating near-saturated air and actual dehumidification.
- If dew point rises between the return grille and return plenum, the difference points toward high-dew-point air entering through a return leak, even if temperature readings mainly show duct heat gain.
- The hottest design day is rarely the most humid one, so systems can maintain temperature while failing to control moisture during mild, humid, part-load conditions.
- Condensation occurs when high-dew-point air meets a cooler surface; diagnosis should focus on lowering the air dew point, raising the surface temperature, or both.
- Encapsulated attics require actual moisture control—such as conditioned air or dehumidification—because moving insulation to the roof deck alone can leave moisture cycling through open-cell foam and roof sheathing.
- Data logging dew point in homes, attics, and ducts can expose problems that relative-humidity readings miss and can verify whether weatherization or dehumidification fixed them.
Summary
Tim and Sophie frame dew point as the practical goal
The live symposium session is presented by Tim De Stasio and Sophie Ashley. Tim is a former residential contractor and business owner who now works in training, HVAC design, and building performance in Southport, North Carolina. Sophie is a South Carolina licensed home builder with a carpentry and home-building background who is now also an HVAC contractor working with Dr. Allison Bailes. Their objective is to move technicians beyond treating relative humidity as the whole story and toward using dew point to understand moisture, predict condensation, assess equipment, and diagnose building problems.
Why 50% relative humidity does not reveal moisture content
Tim uses two glasses to distinguish relative from absolute humidity. A glass that is 50% full tells you the percentage of capacity occupied, but not how much water is actually present; a larger glass and a smaller glass can both be 50% full while containing very different amounts. Air temperature changes the size of the metaphorical container, so warm and cool air can both read 50% relative humidity while having different absolute moisture contents. Tim says latent-load calculations and equipment dehumidification are really concerned with how much water is present, not merely the percentage.
The psychrometric chart turns dew point into a moisture measure
Tim compares the psychrometric chart to an oddly shaped glass: a horizontal line represents the amount of moisture in the air, with a higher line meaning more water. Humidity ratio, or grains per pound, is one absolute measure; there are 7,000 grains in a pound or pint of water. The presentation focuses on dew point, which is a temperature used as a surrogate for moisture content. A higher dew point corresponds to more water vapor and a higher humidity ratio, so technicians can think in terms of high-, middle-, or low-dew-point air rather than relying on a relative-humidity percentage.
Why evaporator supply air can be 100% RH yet much drier
Cooling air makes the metaphorical container smaller. Once the air reaches saturation, further cooling forces water out as condensation, while the leaving air remains saturated and therefore reads 100% relative humidity. Tim emphasizes that this does not mean the air became wetter: a 50°F dew point leaving an evaporator says much more than a 100% RH reading. In normal cooling, air is brought to saturation at the coil, cooled below its original dew point, and loses moisture to the drain pan. Condensation is wanted at the evaporator but generally nowhere else inside the house.
A sweating beer can demonstrates the condensation rule
Using a cold Coors Light can at a South Carolina cookout, Tim shows why condensation forms when humid air touches a colder surface. Beaufort’s example outdoor air is 91°F with a 72°F dew point, while the can is around 33°F; the air touching the can cools below its dew point and releases water. He defines dew point as both a psychrometric property and the temperature at which water begins condensing on a surface. The practical rule is that high-dew-point air meeting a cooler surface creates condensation, so technicians should either lower the air’s dew point, raise the surface temperature, or do both.
The 55°F summer target and Tim’s 60-60 rule
Tim has attendees use the Munters Psychro app and enter Manual J’s typical indoor design condition of 75°F dry bulb and 50% relative humidity. The resulting target dew point is about 55°F. He says 55°F is a reasonable summer goal rather than an absolute line; a thunderstorm can temporarily push it toward 60°F, but it should return. His “60-60 rule” is to avoid sustained indoor conditions above 60% relative humidity and above a 60°F dew point. He still considers relative humidity useful for indoor-air-quality guidance, with roughly 30–60% generally preferred.
Peak humidity is not the same as peak temperature
For Beaufort, South Carolina, Tim gives a 1% cooling design condition of 91°F dry bulb and 76.9°F wet bulb, producing roughly a 71–72°F dew point. ASHRAE data also show a peak-dehumidification condition around a 77.4°F dew point with only an 82°F dry bulb. Thus the most humid period can occur when the air conditioner is not facing its design heat load. Systems sized for a 91°F afternoon may short-cycle, unload, or run an inverter at part load during an 82°F but extremely humid period. Tim uses this mismatch to argue for supplemental dehumidification.
Using dew point to screen return ducts and evaporators
For a return-leak screening test, Tim places one psychrometer at the return grille and then at the return plenum. If the space reads 75°F and 55°F dew point but the plenum reads 77°F and 57–59°F dew point, the temperature rise can be attic heat gain, but the dew-point rise indicates high-dew-point air entered through a return leak. Dew point remains comparable despite temperature changes, unlike relative humidity. Across an evaporator, he expects both dry-bulb and dew point to fall; an example changes from 75°F/55°F return air to 55°F/52°F supply air.
When a cooling system lowers temperature but not humidity
Tim’s quick evaporator screen looks for supply dew point below return dew point and supply dew point within about three degrees of supply dry bulb, indicating air near saturation. A system reading 75°F/60°F entering and 60°F/60°F leaving has a 15°F temperature drop but no moisture removal. Possible causes include excessive airflow, overcharge, an underfeeding TXV, or low charge—the technicians’ familiar “ain’t got no gas” diagnosis. The same pattern can occur on an inverter or other variable-capacity system operating at part load: it maintains 75°F while backing off the compressor and airflow without removing enough latent moisture.
Data logging reveals leaky buildings and winter window risk
Sophie compares data from her South Carolina home and a small California house. Both could show relative humidity above 60%, but the California house’s dew point stayed below the 55°F target because its warmer or cooler conditions changed the RH interpretation; South Carolina’s actual moisture content remained too high. In winter, her house was 70°F, 55% RH, and 53°F dew point while outdoors was 25°F. Window surfaces fell below 53°F and developed microbial growth. She lowered indoor dew point with a ventilating dehumidifier; in colder climates, an ERV may be preferable, and registers aimed at windows can help.
Vented and encapsulated attics can hide moisture problems
Sophie describes a bonus room beside a vented attic, where attic dew points can range from 60°F to 90°F. If humid attic air reaches cooled drywall through fibrous knee-wall insulation, the wall becomes a condensation and mold risk; rigid foam on the attic side, with sealed seams, creates the needed air barrier. Encapsulating an attic moves the insulation and air barrier to the roof deck, but does not automatically solve moisture. Her data showed a vented attic with much higher and more variable dew point than an encapsulated attic, whose median was about 51°F, provided the encapsulated space was actually conditioned.
The open-cell foam “ping-pong” effect and the Q&A lessons
In Sophie’s encapsulated attic, dew point rose and fell daily despite no cooking or bathing there. Overnight, the roof cooled, moisture migrated through vapor-open open-cell foam into the OSB roof deck, and daytime sun drove it back into the attic air—the “ping-pong effect.” A ventilating dehumidifier and a supply drop from existing ductwork reduced the cycling. In Q&A, the presenters recommend measuring where the problem is—near a ridge for attic air or near sweating ducts—and note that attic dew point may run 5–7°F above outdoors. They also discuss vapor-diffusion ports as supplemental, not replacement, moisture control; sealing boots from the attic side; and tracing two-story floor-cavity duct sweating to leaky framing or chases.
Sponsors
- Refrigeration Technologies — Viper Wipes · Viper Wipes are described as an all-purpose wipe that cuts through mastic, oil, grease, tar, and grime while being gentle on hands.
- Carrier · Carrier is mentioned as an episode partner.
- NAVAC · The NAVAC Nexus NX1 digital manifold supports 72 refrigerant types, including A2L refrigerants, handles 600 psi working pressure, and has quarter-turn ball valves. The NX4 adds four valves, a three-quarter-inch vacuum port, manifold, leak-test, evacuation, and decay-test modes, plus integration with the NMV1S micron gauge and MyNAVAC app.
- Fieldpiece · Fieldpiece promotes the CAT85 combustion analyzer, SC680 power and current meter, and JL3RH wireless humidity and duct-temperature probes. The tools integrate with JobLink, and Fieldpiece University offers interactive training.
- 2027 AHR Expo · The 2027 AHR Expo will take place at McCormick Place in Chicago from January 25–27, featuring HVACR equipment, tools, technology, seminars, Innovation Award winners, and live podcast pavilions.
Show notes
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think in terms of dew point, an absolute measure of how much moisture is actually in the air. Using a glass-of-water analogy and the psychrometric chart, they show why 50% relative humidity means very different things in warm and cool air, and why air leaving an evaporator coil can read 100% RH while being far drier than the air that entered.
From there, Tim turns dew point into practical field tools. He sets a summer indoor target of 75°F dry bulb and a 55°F dew point, then shows how to screen a system with two psychrometers: dew point should match between the return grille and the return plenum (a mismatch signals return leakage), and supply dew point should be lower than return dew point and within about three degrees of supply dry bulb. He also explains why the hottest day is rarely the most humid, which makes the case for supplemental dehumidification, and walks through the idea that condensation is simply high dew point air meeting a cooler surface.
Sophie brings the building science view, with data logger charts from her own home in South Carolina, a tiny house in California, and her encapsulated attic. She shows how dew point exposed a winter window condensation problem and a daily "ping-pong" moisture cycle in open-cell foam at the roof deck, and how a ventilating dehumidifier and a conditioned attic supply fixed it. Her message is that dew point lets you find problems you would never see in relative humidity, and confirm that your fixes worked.
The session closes with an extended Q&A covering how to measure dew point in attics, attic dew point differences, vapor diffusion ports, sealing supply boots from the attic side, and a stubborn case of sweating ductwork in a two-story home's floor cavity.
Topics Covered
- Relative versus absolute humidity, and why relative humidity alone "lies"
- Reading dew point on the psychrometric chart and in the MeasureQuick app
- Saturation, evaporator coil dehumidification, and why supply air can read 100% RH
- Summer design targets: 75°F dry bulb and 55°F dew point, plus Tim's "60 rule"
- Outdoor design conditions, peak dehumidification days, and oversized equipment on mild humid days
- Return duct leak screening using dew point at the grille versus the plenum
- Evaporator performance checks: supply dew point below return, within about 3°F of dry bulb
- Why inverter and variable-capacity systems can struggle with humidity at part load
- Condensation diagnosis: lower the dew point of the air or raise the surface temperature
- Register sweat, bathroom ceiling condensation, and sweating ducts in crawl spaces and attics
- Winter window condensation, ventilating dehumidifiers, ERVs, and register placement
- Vented versus encapsulated attics, knee wall air barriers, and the ping-pong effect
- Vapor diffusion ports as a supplement to, not a substitute for, dehumidification
- Data logging with HAVEN and other loggers to track indoor and outdoor dew point
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, Fieldpiece, and the 2027 AHR Expo.
Resources
- A House Needs to Breathe... Or Does It? (Dr. Allison Bailes's book)
- Condensation Control Calculator for Horizontal Pipe (insulation.org calculator)
- HVAC School calculators
- Submit a podcast question
- Learn about the GRIT Foundation
Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Follow this show on AudioBrevity and new episodes get summarized for you. Create a free account