Key takeaways

  • MCA stands for Minimum Circuit Ampacity, which is used to size wire, while MOCP refers to Maximum Overcurrent Protector, used to size breakers.
  • New standards in UL 60335-2-40 require more conservative calculations, impacting how MCA is determined and leading to potential confusion.
  • Manufacturers may list lower recommended breaker sizes on data tags, but those recommendations are not enforceable code requirements.
  • Effective communication strategies are essential for resolving inspection conflicts, including referencing updated manufacturer data.
  • Understanding voltage drop is crucial as inverter-driven equipment behaves differently from traditional motors by compensating for voltage variance.

Summary

Introduction to Breaker and Conductor Sizing

In this episode of the HVAC School Podcast, Brian Orr teams up with Elliot, a residential install supervisor, to discuss the evolving standards around breaker and conductor sizing for inverter-driven HVAC equipment. The conversation is prompted by Elliot's perplexing experience with two inspectors in the same county, each issuing conflicting failures for the same installation based on breaker size.

Understanding Changes in UL Standards

The podcast dives deep into the recent updates in UL standards, particularly UL 60335-2-40 Edition 3, which has revised the calculations for electrical characteristics in HVAC systems that use low GWP refrigerants. Due to these updates, Minimum Circuit Ampacity (MCA) ratings are now higher than before, leading to the confusion that arises with the recommended breaker sizes on data tags.

Sizing Rules: MCA and MOCP Explained

Brian and Elliot clarify the crucial convention of sizing wire to MCA and breaker sizes to the maximum overcurrent protector (MOCP). They emphasize that manufacturer recommendations may suggest lower breakers than the MCA, but these recommendations are not code requirements, intended instead as helpful guidance for contractors.

Conflicting Knowledge among Inspectors

The duo highlights the confusion experienced by inspectors due to the mismatch in MCA and MOCP. They recommend addressing inspector failures with clear, polite communication, backed by the updated manufacturer data, to resolve disputes effectively.

Voltage Drop and Inverter-Driven Equipment

Inverter-driven systems demonstrate distinct electrical behavior compared to traditional PSC motors, especially concerning voltage drops. The hosts explain how inverter systems compensate for lower voltages by drawing higher currents, emphasizing that while voltage drop isn't enforceable under NEC guidelines, it’s still important for efficient operation.

Practical Takeaways for HVAC Professionals

The episode concludes with practical advice on implementing the discussed standards in real-world applications, focusing on the significance of proper wire and breaker sizing for A2L refrigerant equipment, as well as navigating the landscape of electrical codes.

Sponsors

  • Carrier · This episode is brought to you by Carrier, visit Carrier.com.
  • Refrigeration Technologies · Check out Viper Wipes, the all-purpose wipes for everything from grease to grime.
  • Copeland · Check out the White Rogers Sure Switch, a multi-voltage replacement contractor that lasts much longer than typical contactors.
  • TrueTechTools · True Tech Tools provides a wide range of great tools with top-notch customer service, and use the code GetSchooled for discounts.

Show notes

In this essential episode, Bryan Orr sits down with Elliot, the residential install supervisor at Kalos Services, to unpack a critical issue that's causing confusion among HVAC technicians, electricians, and inspectors alike: the new standards for breaker and conductor sizing on inverter-driven equipment. The conversation was sparked by Elliot's frustrating experience of having two inspectors in the same county fail the same installation for opposite reasons—one for an oversized breaker and another for an undersized breaker. This contradiction led to a deep dive into recent changes in UL standards and how they affect everyday HVAC installations.

The heart of the issue stems from the transition to low-GWP refrigerants and the updated UL 60335-2-40 Edition 3 standard, which replaced the 1995 certification approach. This new standard introduced more conservative calculations for electrical characteristics, particularly affecting equipment using A2L refrigerants. The result? Data tags now show higher Minimum Circuit Ampacity (MCA) ratings than before, even though the equipment itself hasn't changed—only the math used to calculate these values has shifted. This has created a puzzling situation where the MCA can be higher than the recommended breaker size, which seems counterintuitive to anyone familiar with traditional electrical principles.

Bryan and Elliot clarify the fundamental rule that still applies: size your wire to the MCA and your breaker to the MOCP (Maximum Overcurrent Protector). The confusion arises because manufacturers like Mitsubishi are now including "recommended breaker" sizes on data tags that are lower than the MCA—a courtesy to contractors, not a code requirement. The higher MCA reflects conservative safety margins that account for extreme operating conditions, but in practice, inverter-driven systems have multiple built-in protections that prevent them from ever actually reaching these calculated amperage levels. The key takeaway is that contractors can safely install breakers at the recommended size without safety concerns, as long as the breaker's lugs are rated to accept the wire size required by the MCA.

The episode also explores how inverter-driven equipment fundamentally differs from traditional PSC motors, particularly regarding locked rotor amps (now more accurately termed "inverter input") and voltage drop considerations. Unlike conventional motors that simply run slower with reduced voltage, inverter-driven compressors and ECM motors compensate by drawing more current to maintain performance, creating a potential compounding effect with voltage drop that installers need to understand—even though voltage drop itself isn't an enforceable NEC code requirement.

Topics Covered:

  • New UL 60335-2-40 Edition 3 standards and their impact on electrical calculations for HVAC equipment
  • The relationship between MCA (Minimum Circuit Ampacity) and MOCP (Maximum Overcurrent Protector) and why they can now seem contradictory
  • Recommended breaker sizes on modern data tags and why they may be lower than the MCA
  • Handling inspector conflicts and failed inspections related to breaker sizing
  • Differences between inverter-driven equipment and traditional PSC motors in electrical behavior
  • The transition from "locked rotor amps" to "inverter input" terminology for modern equipment
  • Voltage drop considerations with inverter-driven systems (NEC 210.19A and 215.2A)
  • Why inverter-driven equipment draws more current at lower voltages compared to traditional motors
  • Proper wire and breaker sizing for A2L refrigerant equipment (454B systems)
  • NEC Section 440 requirements specific to air conditioning and refrigeration equipment
  • Breaker lug ratings and ensuring they can accept the required wire size
  • Practical advice for communicating with inspectors and resolving code disputes

 

Read the tech tip on this topic HERE.

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 7th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

Follow this show on AudioBrevity and new episodes get summarized for you. Create a free account

Couldn't load the audio. A blocker may be stopping the show's tracking links. Open the file